Recommended tools
We recommend using the following tools to safely measure the voltage:
Duspol or Multimeter
Safety precautions
Step-by-step instructions
Step 1: Check for presence of Error 212 on the display and/or in the SIA's logging.
L1-N, L2-N and L3-N should show between 207V and 253V for correct operation.
L1L2, L2L3 and L3L1 should show appr. 400V.
Note that these line-voltages are only displayed when ABB power meter is used in the charger. Reallin power meters will show N/A.
Step 2: Check configuration for the number of phases.
Go to power settings in SIA and confirm if phases set matches the installation.
When set to '3-phase' on a 1-phase install, the charger will miss the two phases that are not connected and may report error 212.
Step 3: Check voltages at incoming supply.
For EVE-Single: Measure on the power entry.
For EVE-Double and Twin, measure on the incoming side of the chargers main switch.
This is where customers cable from the installation is connected.
L1-N, L2-N and L3-N should measure between 207V and 253V for correct operation.
Step 4: If measured incoming voltages are NOT correct.
Add picture to the ticket that shows the reading on your meter AND showing the position of the probes
This to prove to the customer the incorrect voltage is received from the installation.Installer/location should correct the issue as there is an external cause for the error.
Step 5: If measured incoming voltages are correct.
Follow the wire to find the location where the voltage is lost.
The problem should be between the last correct voltage and location where the voltage is lost.
Check for broken wires or wires not connected correctly in components.
